FabricAir Glass

FabricAir® Glass 220 is woven with non-combustible glass fibers, class M0 / A2, making it ideal in areas with strict fire rating requirements. The working temperature range goes from -60°C to +200°C [-76°F to 392°F]. The material cannot be machine washed.

The fabric is available in standard colors.

All FabricAir® Glass 220 variants come with a 1-year warranty.

 

FabricAir® Glass 220 is non-combustible.

Profiles

FabricAir round duct is the most commonly used duct profile and is typically found in open ceiling applications. The duct diameter can be made as small or as big as required.

The Circle Section duct can be used when there is a hard ceiling to attach to. Typically this profile is used when there is not enough head room to allow for the use of a Half-round duct. 

Flow models

PerfoFlow™

PerfoFlow™

 

WithPerfoFlow™ the air exits the duct via laser cut perforations along the circumference of the duct.

The perforations can cover between 90° and 360° of the duct’s circumference.

The size of the near zone depends on the static pressure inside the duct, the percentage of the circumference that is perforated, and the size and spacing of the perforations.  

SonicFlow™

SonicFlow™

SonicFlowTM is a directional flow model where the air exits the duct via rows of laser cut perforations. Multiple rows of SonicFlowTM can be specified for a duct, with each row covering a maximum of 30° of the circumference. The throw depends on the static pressure inside the duct, the size, and spacing of the perforations.

OriFlow™

OriFlow™

OriFlowTM is a directional flow model where the air exits the duct via rows of laser cut orifices. Multiple rows of OriFlowTM can be specified for a duct. The throw depends on the static pressure inside the duct, the size, and spacing of the orifices.

NozzFlow™

NozzFlow™

NozzFlowTM is used in applications where very precise directional airflow is needed. The discharge coefficient is almost at unity due to the shape of the nozzle. This results in higher discharge velocities than an equivalently sized orifice, and longer more directional throws.

Data sheet

Construction

Fabric type:
Glass
Weight
460  g/m²
Thickness:
0,40 [0.016]  mm [inch] EN ISO 5084:1996 (ASTM D1777-96)
Permeability:
0  (±5%) m³/m²/h at 120 Pa
0  (±5%) [CFM/ft² at 0.5” Static]EN ISO 9237:1995 (ASTM D737, Frazier)

Properties

Heat resistance - continuous:
-60 to +200 [-140 to +392]  °C [°F]

Treatment/Coatings

Code Compliance

GB 8624:
A2-s1,d0, t1 GB 8624
GOST:
Yes
ULC S102.2:
Yes
Fire retardant:

Performance certificates

Additional Approvals

All-in-One available:
Disclaimer

FabricAir® believes that all data, statements, technical information, etc., listed in this Technical Data Sheet regarding the product and the use of the product are accurate and reliable. However, the product will only be covered by FabricAir®’s guarantees or warranty if the final use for the product has been approved by FabricAir® in writing. No representative is authorized to approve the final use of the product on behalf of FabricAir®.

Variations of the fabric

Glass220
Permeable Flame Retardancy Antistatic Anti-microbial Warranty
  Glass 220 Non combustable 1

Certificate comparison

Related articles

Some applications require completely non-combustible ducts, where the flame spread index is zero.